BUSCADOR

Switch disconnectors


SF6 THREE PHASE LOAD BREAK SWITCH

General characteristics

The pole mounted SF6-Gas insulated Load Break Switch is designed to meet the increasing requirement of the electric utility industry, providing a safe, low maintenance, long life, economical alternative device to perform load switching on overhead electrical distribution feeders. They can be supplied in the versions manual, prepared for future automation and automatic with control box and device for remote communication.

They can be supplied in the following versions:

  • Manual
  • Prepared for future automation
  • Automatic with control box and device for remote operation.

Electrical characteristics

  Rated Voltage (kV):  15 25,8 36  
 Rated Current (A)  630
 Rated Short Time Withstand Current, 1s (kA):  12,5 / 16 / 20 (1)
 BIL (kV):  110 150 170
Current and Voltage Sensor Incorporate (2)  
 Control box with functions of measure, supervision and control (3)  
 Applicable Standard  NBR 10840, IEC 60625-1

Notes:
(1) Under consultation.
(2) Available in the versions prepared for automation and automatic.
(3) Available in the automatic version with control box.

Imagen de SF6 THREE PHASE LOAD BREAK SWITCH
DOCUMENTATION

SINGLE PHASE ISOLATING OIL SWITCH OF MEDIUM VOLTAGE - CSL

General characteristics

The CSL single phase mineral oil switch type is one equipment to switch load in circuits of medium voltage that especially possess own characteristics of application in loads capacitives operation originating from capacitors banks and also to use in public lighting circuits. Also, it can be used as a load insulating switch in the rural and urban distribution systems. They can operate through a group of coils and they can form groups to be manually or electrically operated as one pole or forming two poles or three pole units.

Electrical characteristics

MODELS CSL - 15 CSL - 20
Rated Voltage 14,4 20*
Rated Maximum Voltage, kVrms: 15,5 22
Rated frequency, Hz: 50 60
Rated Continuous Current, Arms: 200 60
Capacitive current switching, Arms: 200 60
Inductive current switching ( 0,75 <= cos Ø<=1), Arms: 200 60
Short-time current:
    - 1/2 s symmetrical, Arms: 6000 6000
    - 1 s symmetrical, Arms: 4500 4500
Making Current:
    - Inrush, symmetrical, Arms: 6000 6000
    - Peak current, Apeak: 12000 12000
Momentary asymmetrical, Arms: 9000 9000
Standards ANSI C37. 66-1989 and IEC 60265

Note: (*) It can be used to switching grounded capacitor bank in a 20/34.5kV system.